HM-H16512PSD-112K/240K Rock-Solid High-Voltage Storage Battery Cabinet
An integrated design that brings the battery system, intelligent management, forced-air thermal management and fire suppression into a single cabinet, giving C&I users a more compact and flexible storage configuration. The system uses 314 Ah LiFePO4 cells in 7 or 15 battery packs, with a rated energy of 112 or 241 kWh and an optional external inverter, meeting the charge and discharge needs of commercial and industrial sites.
- Battery, forced-air thermal management, cabinet-level aerosol fire suppression and intelligent management in one compact cabinet
- Two capacities — 112K and 240K (7 or 15 battery packs) — to suit projects of different scale
- IP55 protection with efficient forced-air cooling — dust-tight, water-jet protected and thermally optimised
- BMS samples cell, pack and cluster status in real time and works with the PCS, with multiple protections
Product Specifications
| Specification | HM-H16512PSD-112K | HM-H16512PSD-240K |
|---|---|---|
| Model | HM-H16512PSD-112K | HM-H16512PSD-240K |
| Battery type | LiFePO4 | |
| Nominal battery energy | 112.49 kWh | 241.05 kWh |
| Cell capacity | 314 Ah | |
| Nominal voltage | 358.4 V | 768 V |
| Operating voltage range | 313.6 – 403.2 V | 672 – 864 V |
| Pack configuration | 1P112S (7 battery packs) | 1P240S (15 battery packs) |
| Peak current | 120 A | |
| Rated charge/discharge current | 100 A | |
| Communication | CAN, RS485 | |
| Weight | 1.25 t | 2.37 t |
| Dimensions L×W×H (mm) | 1204 × 864 × 2286 | 1286 × 1200 × 2223 |
| Protection | Cell over/under-voltage, total over/under-voltage, charge/discharge over-current, high/low temperature and short-circuit protection with recovery | |
| Self-discharge | ≤3%/month (new cells, charged to 27% SOC, stored at 25°C ± 2°C for 3 months) | |
| System parameters | ||
| Cooling | Forced air cooling | |
| Protection rating | IP55 | |
| Cycle life | 8,000cls @ 80% SOH | |
| Depth of discharge (DOD) | 90% | |
| Environment | ||
| Charging temperature range | -40°C to +55°C | |
| Discharging temperature range | -40°C to +55°C | |
| Operating humidity | 5% – 95% | |
| Storage temperature | -40°C to +55°C | |
| Max. operating altitude | 4,000 m (derating from 1,800 m to 4,000 m: 1°C per 220 m) | |
| Standards and certifications | ||
| Safety | GB/T 36276-2023, GB 44240-2024 | |
| Transport | UN38.3 | |
| Fire suppression | Aerosol (cabinet-level) | |
Note: the inverter is an optional accessory supplied separately; specifications are subject to the latest datasheet.
HM-H16512PSD-112K/240K Rock-Solid High-Voltage Storage Battery Cabinet enquiry
Leave your contact details and the HONGMLD team will provide professional sizing advice, a tailored solution and a quotation.
- ✓Fast response on business days, 9:00–18:00 (GMT+8)
- ✓Free system design and on-site survey
- ✓One-stop service from selection and delivery to O&M
Where it fits
HM-H16512PSD-112K/240K Rock-Solid High-Voltage Storage Battery Cabinet suits the following power scenarios.
Commercial & Industrial PV + Storage
A green engine for cost reduction: peak shaving and valley filling to lower electricity costs.
PV-Storage-Charging Integrated Station
A green artery for urban transport, with PV, storage and charging working in concert.
Related cases
Covering factories, villas, hotels, public institutions, food processing plants and telecom base stations, with real project results proving the value of our products.
HONGMLD factory self-consumption
A 52 kW PV + 64 kWh storage system covering production and office loads. It generates 216 kWh per day on average and cuts electricity costs by about 72%, directly reducing operating expenses.
Villa PV + storage upgrade
Existing 20 kW PV plus 32 kWh of new storage. Surplus PV is stored to cover loads from the evening until 8 a.m. the next day, combining self-consumption with backup power during outages.
PV + storage integration at Home Inn, Yuncheng
31 kW PV + 32 kWh battery storage. Daytime solar is stored to secure air-conditioning loads during the night check-in peak, shaving peak demand and reducing the hotel's energy bill.
PV-storage-charging project for a Party school
80 kW PV + 64 kWh storage with a PV carport and charging piles. It supplies about 94,316 kWh of green electricity per year, a green coverage rate of roughly 63%.
Food Processing Plant Solar + Storage Project
200 kWp PV + 261 kWh storage. Rooftop PV supplies the production load first; surplus energy is stored and released at peak times, cutting overall energy costs.
Tongliao Telecom Base Station Storage Project
20 kW PV + 32 kWh storage. PV covers the base station's daily load and surplus power is stored to raise green-power utilisation; the battery backs up critical communications during outages.